2 Parameters
2.2 List of parameters
SINAMICS DCM
124 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the reference quantity for current.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Description: Sets the reference quantity for torque.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Description: Displays the reference quantity for power.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency: This value is calculated as follows:
Closed-loop control: Calculated from torque times speed.
Refer to: p2000, p2001, p2002, p2003
Note: If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
The reference power is calculated as follows:
- 2 * Pi * reference speed / 60 * reference torque (motor)
Description: Sets the reference quantity for angle.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
p2002 Reference current / I_ref
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.10 [Arms] 100000.00 [Arms] 100.00 [Arms]
p2003 Reference torque / M_ref
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: 7_2 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.01 [Nm] 20000000.00 [Nm] 1.00 [Nm]
r2004 Reference power / P_ref
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568,
9572
P-Group: Communications Unit group: 14_10 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [kW] - [kW] - [kW]
p2005 Reference angle / Reference angle
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
90.00 [°] 180.00 [°] 90.00 [°]