4 Faults and alarms
4.2 List of faults and alarms
Reaction upon A: NONE
Acknowl. upon A: NONE
F60095 (N, A) Power supply P24 overloaded
Message value: -
Message class: General drive fault (19)
Drive object: DC_CTRL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: Power supply P24 (+24 V) at terminal X177.9 or X177.10 is overloaded.
Note:
r50047[1]: Reference voltage +10 V (in volts)
r50047[2]: Reference voltage -10 V (in volts)
r50047[3]: Module temperature (in °C)
Remedy: Identify the reason for the overload (e.g. digital outputs) and rectify the situation.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60096 (N, A) Temperature sensor faulty
Message value: %1
Message class: Internal (DRIVE-CLiQ) communication error (12)
Drive object: DC_CTRL
Reaction: OFF2 (NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY
Cause: A cable break or a short circuit has been detected on at least one temperature sensor.
Fault value (r0949, interpret decimal):
1: A cable break has occurred.
2: A short circuit has occurred.
Note:
r50047[1] = 1: Temperature sensor 1
r50047[1] = 2: Temperature sensor 2
r50047[1] = 3: Temperature sensor 3
r50047[1] = 4: Temperature sensor gating module
r50047[1] = 5: Temperature sensor CUD module
r50047[1] = 6: Motor temperature sensor
r50047[2]: Value of the analog-to-digital converter
Remedy: Evaluate the fault and, if the temperature sensor is faulty, run a wiring and performance check.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60097 (N, A) Power supply faulty
Message value: -
Message class: Power electronics faulted (5)
Drive object: DC_CTRL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: The power supply is not working correctly.
Note 1:
r50047[1]: Reference voltage +10 V (in volts)
r50047[2]: Reference voltage -10 V (in volts)
r50047[3]: Module temperature (in °C)