2 Parameters
2.2 List of parameters
SINAMICS DCM
592 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Display and connector output for the absolute value of the setpoint on the EMF controller.
Dependency: Refer to: r50039, p50100, p50101, p50110
Note: A value of 100% corresponds to p50078[0] * (3 * sqrt(2)) / Pi.
Description: Display and connector output of the motor flux in the case of closed-loop field current control.
The value is a percentage of p50102.
Description: Display and connector output for the actual value of the armature voltage as an absolute value.
Dependency: Refer to: r52292
Note: 100% corresponds to p50078[0] * (3 * sqrt(2)) / Pi
Description: Display and connector output for the signed actual value of the armature voltage.
Dependency: Refer to: r52291
Note: 100% corresponds to p50078[0] * (3 * sqrt(2)) / Pi
Description: Display and connector output for pre-control on the EMF controller.
r52289 CO: EMF controller setpoint absolute value / EMF ctr set abs
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6900
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52290 CO: Closed-loop field current control motor flux output / If ctr motor flux
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6830, 6835,
6851, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52291 CO: Armature voltage actual value absolute value / Ua act abs
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6902
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52292 CO: Armature voltage signed actual value / Ua act signed
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6902
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52293 CO: EMF controller pre-control output / EMF ctr prec outp
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6900, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]