2 Parameters
2.2 List of parameters
SINAMICS DCM
480 List Manual (LH8), 02/2015, 6RX1800-0ED76
Value: 0: Adaptation non-linear L active
1: Fixed value 100 % effective
Dependency: Refer to: p50575, p50577, r52355
Description: Activates the adaptation to the non-linearity of the gating unit for the field current controller.
Value: 0: Adaptation gating unit effective
1: Fixed value 100 % effective
Dependency: Refer to: p50575, p50576, r52355
Description: Setting to limit the field current controller adaptation.
Dependency: Refer to: p50576, p50577, r52355
Description: Sets the signal source for the direction of rotation for the "field reversal" function.
0 signal:
Positive field direction is selected (r53195.0 = 1, r53195.1 = 0).
The speed actual value is not inverted.
1 signal:
Negative field direction is selected (r53195.0 = 0, r53195.1 = 1).
The speed actual value is inverted.
Dependency: Refer to: p50092, p50581, p50583, r53195
Description: Sets the signal source for the "field reversal braking" function.
0/1 signal:
Reversal of the field direction (this has a braking effect).
At n < n_min, the original field direction is selected again. The drive goes into operating state o7.2.
p50577[0...n] Adapt field curr controller non-linear gating unit activation / Adapt n_lin GU act
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6908
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50578[0...n] Adaptation field current controller limiting / Adapt If_ctrl lim
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6908
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
1.0 [%] 1000.0 [%] 200.0 [%]
p50580[0...n] BI: Field reversal direction of rotation signal source / Field rev sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 6920
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p50581[0...n] BI: Field reversal braking signal source / Field rev br sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 6920
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0