SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
1155
4 Faults and alarms
4.2 List of faults and alarms
The optimization run was completed in full.
Recommendation:
Check the parameter values set!
Fault value (r0949, interpret decimal):
Parameter number of the parameter causing the error.
Note:
r50047[1]: Incorrect value
r50047[2]: Limited value
r50047[3]: Lower limit value
r50047[4]: Upper limit value
Remedy: You might have to set the parameter value manually.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60052 (N, A) Optimization run aborted due to external cause
Message value: %1
Message class: General drive fault (19)
Drive object: DC_CTRL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: An optimization run which had been started has been interrupted due to an external cause.
Fault value (r0949, interpret decimal):
101: ON command not set within 30 seconds
102: Following the ON command, operating state o0.x or o1.5 was not achieved within 1 minute.
103: Impermissible parameter setting for this optimization run
104: Internal software error
105: Internal software error
106: Internal software error
108: Operating state o0.x or o1.5 exited during the optimization run
109: The operating system does not allow the optimization run to access a parameter.
110: Internal software error
111: Internal software error
112: Data set changeover (DDS) during an optimization run
113: Data set changeover (CDS) during an optimization run
114: Enable for the positive direction of rotation missing.
Note for fault value = 103:
- r50047[1]: 1 = Sequence control optimization run, 2 = Field optimization run, 3 = EMF optimization run
- If r50047[1] = 1, r50047[2 to 3] are not relevant
- r50047[2]: Parameter number
- r50047[3]: Parameter value
Note for fault value = 104:
- r50047[1]: Parameter number (parameter number = 0 indicates a general fault is pending)
Note for fault value = 105:
- r50047[1]: 1 = General fault, 2 = Read parameter, 3 = Write parameter
- If r50047[1] = 1, r50047[2 to 3] are not relevant
- If r50047[1] = 2, r50047[2]: Parameter number
- If r50047[1] = 3, r50047[2]: Parameter number, r50047[3]: Parameter value
Note for fault value = 106:
- r50047[1]: 1 = Sequence control optimization run, 2 = Optimization run
- r50047[2]: OA return status word
Note for fault value = 107:
- r50047[1]: Parameter number
- r50047[2]: OA return status word