SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
515
2 Parameters
2.2 List of parameters
Description: Sets the delay time for digital output 0 (X177.19) on the CUD.
Note: The level at the digital output can only change if the changed internal level remains constant for longer than the set
delay time.
Description: Sets the delay time for digital output 1 (X177.20) on the CUD.
Note: The level at the digital output can only change if the changed internal level remains constant for longer than the set
delay time.
Description: Sets the delay time for digital output 2 (X177.21) on the CUD.
Note: The level at the digital output can only change if the changed internal level remains constant for longer than the set
delay time.
Description: Sets the delay time for digital output 3 (X177.22) on the CUD.
Note: The level at the digital output can only change if the changed internal level remains constant for longer than the set
delay time.
Description: Setting to invert the signals at the CUD's digital outputs.
p50775 CUD digital output 0 delay time / CUD DO 0 t_del
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2055
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50776 CUD digital output 1 delay time / CUD DO 1 t_del
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2055
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50777 CUD digital output 2 delay time / CUD DO 2 t_del
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2055
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50778 CUD digital output 3 delay time / CUD DO 3 t_del
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2055
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50780[0...3] CUD digital inputs/outputs inversion / CUD DI/DO inv
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 2060, 2065
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0