2 Parameters
2.2 List of parameters
SINAMICS DCM
38 List Manual (LH8), 02/2015, 6RX1800-0ED76
Dependency: Refer to: p0700, p1000, p1500, r8570
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
Note: The macros in the specified directory are displayed in r8570. r8570 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
Description: Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0015 = 6 --> the macro file PM000006.ACX is run.
Dependency: Refer to: p0700, p1000, p1500, r8570
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
Note: The macros in the specified directory are displayed in r8570. r8570 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
Description: Setting for activating/de-activating the user-defined list for the Basic Operator Panel (BOP).
If p0016 = 1, then it is only possible to access parameters in the parameter list (p0013).
Value: 0: BOP user-defined list de-activated
1: BOP user-defined list activated
Dependency: Refer to: p0011, p0012, p0013
Note: The user-defined list can only be de-activated with p0011 = p0012
Description: Displays the basic firmware version of the Control Unit.
The version of existing firmware on the device memory is displayed in r7844.
Dependency: Refer to: r0148, r0158, r0197, r0198, r7844
Note: Example:
The value 1010100 should be interpreted as V01.01.01.00.
p0015 Macro drive object / Macro DO
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S, TM150,
TM15DI_DO, TM31
Can be changed: C2(1) Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 999999 0
p0016 Activate BOP user-defined list / BOP user list act
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: C1, U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r0018 Control Unit basic firmware version / CU Basic FW Vers
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4294967295 -