2 Parameters
2.2 List of parameters
SINAMICS DCM
448 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the OFF delay for the "Reference speed reached" message.
Dependency: Refer to: p50373, p50374, p50592, r53025
Description: Sets the threshold for the "Setpoint/actual value deviation 2 reached" message.
Dependency: Refer to: p50377, p50378, p50596, p50597, r53025
Note: The "Setpoint/actual value deviation 2 reached" message is available as follows:
- r53025.2 (not inverted)
- r53025.3 (inverted)
Description: Sets the hysteresis for the "Setpoint/actual value deviation 2 reached" message.
The message is triggered when the threshold is overshot.
Once the value falls below the threshold minus the hysteresis, the message is withdrawn.
Dependency: Refer to: p50376, p50378, p50596, p50597, r53025
Description: Sets the OFF delay for the "Setpoint/actual value deviation 2 reached" message.
Dependency: Refer to: p50376, p50377, p50596, p50597, r53025
p50375[0...n] Messages for reference speed OFF delay / Ref_speed t_OFF
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8020
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 100.0 [s] 3.0 [s]
p50376[0...n] Messages for setpoint/actual value deviation 2 threshold / Set/act 2 thresh
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8020
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 200.00 [%] 3.00 [%]
p50377[0...n] Messages for setpoint/actual value deviation 2 hysteresis / Set/act 2 hyst
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8020
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 200.00 [%] 1.00 [%]
p50378[0...n] Messages for setpoint/actual value deviation 2 OFF delay / Set/act 2 t_OFF
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8020
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 100.0 [s] 3.0 [s]