4 Faults and alarms
4.2 List of faults and alarms
A08550 PZD Interface Hardware assignment error
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM150, TM15DI_DO, TM31
Reaction: NONE
Acknowledge: NONE
Cause: The assignment of the hardware to the PZD interface has been incorrectly parameterized.
Alarm value (r2124, interpret decimal):
1: Only one of the two indices is not equal to 99 (automatic).
2: Both PZD interfaces are assigned to the same hardware.
3: Assigned COMM BOARD missing.
4: CBC10 is assigned to interface 1.
See also: p8839 (PZD interface hardware assignment)
Remedy: Check the parameterization and if required, correct (p8839).
A08564 CBE20: Syntax error in configuration file
Message value: -
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: A syntax error has been detected in the ASCII configuration file for the Communication Board Ethernet 20 (CBE20).
The saved configuration file has not been loaded.
Remedy: - Check the CBE20 configuration (p8940 and following), correct if necessary, and activate (p8945 = 2).
Note:
The configuration is not applied until the next POWER ON!
- reconfigure the CBE20 (e.g. using the STARTER commissioning software)
See also: p8945 (CBE2x interface configuration)
A08565 PNCOMM BOARD : Consistency error affecting adjustable parameters
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: A consistency error was detected when activating the configuration (p8945) for the Communication Board Ethernet
20 (CBE20).
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists.
4: a cyclic PROFINET connection is not possible as DHCP is activated.
Note:
For all alarm values, the following applies: currently set configuration has not been activated.
DHCP: Dynamic Host Configuration Protocol
See also: p8940 (CBE2x Name of Station), p8941 (CBE2x IP Address of Station), p8942 (CBE2x Default Gateway of
Station), p8943 (CBE2x Subnet Mask of Station), p8944 (CBE2x DHCP Mode)
Remedy: - Check the required interface configuration (p8940 and following), correct if necessary, and activate (p8945).
or
- Reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
See also: p8945 (CBE2x interface configuration)