2 Parameters
2.2 List of parameters
SINAMICS DCM
422 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the rate time for the lead/lag element.
Dependency: Refer to: p50207, p50209, r52156
Description: Sets the filter time for the lead/lag element.
Dependency: Refer to: p50207, p50208, r52156
Description: Displays the effective droop on the speed controller.
Notice: The effective droop is displayed as absolute factor without any dimensions and it is especially important to note that
it is not a percentage.
Example:
r50217 = 0.05 --> corresponds to an effective droop of 5 %.
Description: Displays the effective integral time (Tn) on the speed controller.
Description: Displays the effective P gain (Kp) on the speed controller.
p50208[0...n] Lead/lag element rate time / Lead/lag t_rate
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
2 [ms] 10000 [ms] 2 [ms]
p50209[0...n] Lead/lag element filter time / Lead/lag t_filter
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
2 [ms] 10000 [ms] 2 [ms]
r50217 Speed controller droop effective / n_ctr droop eff
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6805
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r50218 Speed controller integral time effective / n_ctr Tn eff
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6805
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [s] - [s] - [s]
r50219 CO: Speed controller P-gain effective / n_ctr Kp eff
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6805
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -