4 Faults and alarms
4.2 List of faults and alarms
If commissioning has already been completed:
- re-establish the original connections and re-connect power to the Control Unit.
- restore the factory setting for the complete equipment (all of the drives) and allow automatic self-commissioning
again.
- change the device parameterization to match the connections (this is only possible using the commissioning
software).
Notice:
Topology changes that result in this fault being generated cannot be accepted by the automatic function in the
device, but must be transferred using the commissioning software and parameter download. The automatic function
in the device only allows constant topology to be used. Otherwise, when the topology is changed, all of the previous
parameter settings are lost and replaced by the factory setting.
See also: r0098 (Actual device topology)
F01356 Topology: There is a defective DRIVE-CLiQ component
Message value: Fault cause: %1, Component number: %2, Connection number: %3
Message class: Hardware / software error (1)
Drive object: All objects
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: The actual topology indicates at least one defective DRIVE-CLiQ component.
Fault value (r0949, interpret hexadecimal):
zzyyxx hex:
zz = connection number of the component at which the defective component is connected
yy = component number of the component at which the defective component is connected
xx = fault cause
xx = 1: Component at this Control Unit not permissible.
xx = 2: component with communication defect.
Note:
Pulse enable is withdrawn and prevented.
Remedy: Replace the defective component and restart the system.
F01357 Topology: Two Control Units identified on the DRIVE-CLiQ line
Message value: component number: %1, connection number: %2
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: In the actual topology, 2 Control Units are connected with one another through DRIVE-CLiQ.
As standard, this is not permitted.
It is only permitted, if the OA application OALINK is already installed on both Control Units.
Fault value (r0949, interpret hexadecimal):
yyxx hex:
yy = connection number of the Control Unit at which the second Control Unit is connected
xx = component number of the Control Unit at which the second Control Unit is connected
Note:
Pulse enable is withdrawn and prevented.
Remedy: - remove the DRIVE-CLiQ connection, restart the systems, install OALINK on both Control Units and commission.
- remove the connection to the second Control Unit and restart.