2 Parameters
2.2 List of parameters
Description: Sets the reference quantity for temperature.
All temperatures specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Description: Sets the reference quantity for acceleration.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Description: Sets the address for the commissioning interface (PPI).
Note: Only odd-numbered addresses can be set.
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the address for the commissioning interface (PPI).
Note: Only odd-numbered addresses can be set.
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p2006 Reference temp / Ref temp
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S, TM150,
TM31
Can be changed: T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
50.00 [°C] 300.00 [°C] 100.00 [°C]
p2007 Reference acceleration / a_ref
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.01 [rev/s²] 500000.00 [rev/s²] 0.01 [rev/s²]
p2011 Comm IF address / Comm add
CU_DC_R,
CU_DC_R_S
Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 127 5
p2011 Comm IF address / Comm add
CU_DC, CU_DC_S Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 127 3