SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
31
2 Parameters
2.2 List of parameters
Description: Sets the access level for reading and writing parameters via the Basic Operator Panel (BOP).
Value: 1: Standard
2: Extended
3: Expert
4: Service
Note: A higher set access level also includes the lower one.
Access level 1 (standard):
Parameters for simplest possible operations.
Access level 2 (extended):
Parameters to operate the basic functions of the drive unit.
Access level 3 (experts):
Expert know-how is required for these parameters (e.g. BICO parameterization).
Access level 4 (service):
For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).
Description: Sets the display filter for parameters with the Basic Operator Panel (BOP).
Value: 0: All parameters
1: Displays, signals
2: Power unit
3: Motor
4: Encoder/pos enc
5: Technology/units
7: Digital inputs/outputs, commands, sequence control
12: Functions
14: Control
15: Data sets
20: Communication
21: Faults, alarms, monitoring functions
28: Free function blocks
47: Trace and function generator
50: OA parameters
90: Topology
98: Command Data Sets (CDS)
99: Drive Data Sets (DDS)
Dependency: Refer to: p0003
Notice: The display filter via p0004 provides precise filtering and displays the corresponding parameters only when p0009
and p0010 = 0.
p0003 BOP access level / BOP acc_level
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: C1, U, T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 4 1
p0004 BOP display filter / BOP disp_filter
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: C2(1), U, T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 99 0