2 Parameters
2.2 List of parameters
SINAMICS DCM
40 List Manual (LH8), 02/2015, 6RX1800-0ED76
Note: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022, r0063[1] with p0045) and unsmoothed (r0063[0]).
Description: Displays the smoothed absolute actual current value.
Dependency: Refer to: p0045, r0068
Notice: This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The absolute value of the current actual value is available smoothed (r0027, r0068[1] with p0045) and unsmoothed
(r0068[0]).
Description: Displays the smoothed torque actual value.
Dependency: Refer to: p0045, r0080
Note: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque actual value is available smoothed (r0031, r0080[1] with p0045) and unsmoothed (r0080[0]).
Description: Displays the smoothed actual value of the active power.
Notice: This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note: Smoothing time constant = 100 ms
The active power is available smoothed (r0032, r0082[1] with p0045) and unsmoothed (r0082[0]).
r0027 CO: Absolute actual current smoothed / I_act abs val smth
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6850
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r0031 Actual torque smoothed / M_act smooth
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6850
P-Group: Displays, signals Unit group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: p2003 Expert list: 1
Min Max Factory setting
- [Nm] - [Nm] - [Nm]
r0032 CO: Active power actual value smoothed / P_actv_act smth
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2450
P-Group: Displays, signals Unit group: 14_10 Unit selection: p0505
Not for motor type: - Scaling: r2004 Expert list: 1
Min Max Factory setting
- [kW] - [kW] - [kW]