2 Parameters
2.2 List of parameters
Description: Display and BICO output for the control word of faults and alarms.
Dependency: Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
Description: Display and BICO output for the control word of faults and alarms.
Dependency: Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
Description: Display and BICO output for status word 1 of faults and alarms.
r2138.7...15 CO/BO: Control word faults/alarms / STW fault/alarm
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S, DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2546, 8060,
8065
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
07 Acknowledge fault Yes No 8060
10 External alarm 1 (A07850) effective Yes No 8065
11 External alarm 2 (A07851) effective Yes No 8065
12 External alarm 3 (A07852) effective Yes No 8065
13 External fault 1 (F07860) effective Yes No 8060
14 External fault 2 (F07861) effective Yes No 8060
15 External fault 3 (F07862) effective Yes No 8060
r2138.7...15 CO/BO: Control word faults/alarms / STW fault/alarm
TM150, TM15DI_DO,
TM31
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2546
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
07 Acknowledge fault Yes No 8060
10 External alarm 1 (A07850) effective Yes No 8065
11 External alarm 2 (A07851) effective Yes No 8065
12 External alarm 3 (A07852) effective Yes No 8065
13 External fault 1 (F07860) effective Yes No 8060
14 External fault 2 (F07861) effective Yes No 8060
15 External fault 3 (F07862) effective Yes No 8060
r2139.0...15 CO/BO: Status word faults/alarms 1 / ZSW fault/alarm 1
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S, DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2548, 8060,
8065
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Being acknowledged Yes No -
01 Acknowledgment required Yes No -
03 Fault present Yes No 8060
05 Safety message present Yes No -
06 Internal message 1 present Yes No -
07 Alarm present Yes No 8065
08 Internal message 2 present Yes No -
11 Alarm class bit 0 High Low -
12 Alarm class bit 1 High Low -