2 Parameters
2.2 List of parameters
Description: Sets the signal source for inverting the signal from analog input 0 (X177.25/26) on the CUD.
1 signal: Inversion
0 signal: No inversion
Description: Sets the time constant for smoothing the signal from analog input 0 (X177.25/26) on the CUD.
Description: Sets the signal source for enabling analog input 0 (X177.25/26) on the CUD.
Note: 1 signal: Analog input enabled
0 signal: Analog input not enabled (r52011 = 0%)
Description: Sets the setpoint for the simulation of analog input 0 (X177.25/26) on the CUD.
Dependency: Refer to: p50709
Note: Simulation is selected using p50709 = 1.
Description: Setting to activate/de-activate the synchronization of the analog inputs of two Control Unit DC MASTERs (CUDs).
p50704 BI: CUD analog input 0 inversion / CUD AI 0 inv
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p50705 CUD analog input 0 smoothing time constant / CUD AI 0 T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50706 BI: CUD analog input 0 signal source for enable / CUD AI 0 ena sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p50707 CUD analog input 0 simulation setpoint / CUD AI 0 sim setp
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-130.0 [%] 130.0 [%] 0.0 [%]
p50708 Activation of analog input synchronization / AI sync act
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 2083
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0