2 Parameters
2.2 List of parameters
Description: Sets the changeover speed for torque limit selection.
Dependency: Refer to: r52166
Note: If torque limit changeover is selected (p50694 = 1) and the speed (p52166) is higher than the changeover speed set
in p50184, then torque limit 2 (p50182, p50183) is activated in place of torque limit 1 (p50180, p50181).
Description: Sets the time constant for smoothing the armature current setpoints at the armature current pre-control input for
closed-loop armature current control.
Note: The smoothing time constant is used to decouple armature current pre-control from the armature current controller.
Description: Sets the time constant for smoothing the armature setpoint for closed-loop armature current control.
Note: The smoothing time constant is used to decouple armature current pre-control from the armature current controller.
Description: Sets the control word for the Alpha W limit on the armature.
Value: 0: Alpha W limit = 165 ° with pulsating armature current
1: Alpha W limit = p50151
Note: If value = 0:
Continuous current: Alpha W limit = parameter p50151
Pulsating current: Alpha W limit = 165 °
If value = 1:
Alpha W limit = parameter p50151
p50184[0...n] Torque limiting changeover speed / T lim n_chng
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6825
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 120.00 [%] 0.00 [%]
p50190[0...n] Cl-loop arm current ctr prectr setpoint smoothing time constant / Ia prec set T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6855
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50191[0...n] Cl-loop arm current ctr curr controller setp sm time constant / Ia ctr set T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6855
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50192[0...n] Armature Alpha W limit control word / A Alpha W lim STW
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6860
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0