SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
297
2 Parameters
2.2 List of parameters
Value: 0: Deactivated
1: Upgrade and downgrade
2: Upgrade
Notice: If this parameter is changed, it only becomes effective the next time that the drive system boots.
Note: The firmware is automatically updated when the system boots. The boot can take several minutes.
After the update has been completed, it is necessary to carry out a new POWER ON (power-down/power-up) for the
components involved.
The firmware update procedure is displayed as follows:
Control Unit (LED RDY):
Flashes yellow with 0.5 Hz --> firmware is being updated.
Flashing yellow with 2 Hz --> POWER ON is required for the components involved.
Components involved:
Flashing red/green with 0.5 Hz --> firmware is being updated.
Flashing red/green with 2 Hz --> POWER ON of the components is required.
Only components from firmware version 2.5 support the red/green flashing at 2 Hz.
Description: Displays the progress when updating the firmware of the DRIVE-CLiQ components.
Description: Sets the component number for the required DRIVE-CLiQ component.
Index 0:
Component number of the DRIVE-CLiQ component for which a firmware download is to be made.
Index 1:
Component number of the DRIVE-CLiQ component for which the reference firmware version, saved in r7825 on the
memory card/device memory, is to be displayed.
Index: [0] = Firmware download
[1] = Reference firmware version
Dependency: Refer to: p0121, p0141, p0151, p7829
Note: For p7828[0] = 399, the firmware for all of the existing components is downloaded.
The firmware download is started with p7829 = 1.
Description: Activating the firmware download for the DRIVE-CLiQ components specified in p7828.
r7827 Firmware update progress display / FW update progress
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p7828[0...1] Firmware download component number / FW downl comp_no
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 399 0
p7829 Activate firmware download / FW download act
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-1 999 0