SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
405
2 Parameters
2.2 List of parameters
Description: Setting of the field current for a motor flux of 20 %.
Note: This parameter is set automatically during the optimization run for field weakening (p50051 = 27).
Only values greater than p50123 and less than p50125 can be set.
Description: Setting of the field current for a motor flux of 25 %.
Note: This parameter is set automatically during the optimization run for field weakening (p50051 = 27).
Only values greater than p50124 and less than p50126 can be set.
Description: Setting of the field current for a motor flux of 30 %.
Note: This parameter is set automatically during the optimization run for field weakening (p50051 = 27).
Only values greater than p50125 and less than p50127 can be set.
Description: Setting of the field current for a motor flux of 35 %.
Note: This parameter is set automatically during the optimization run for field weakening (p50051 = 27).
Only values greater than p50126 and less than p50128 can be set.
p50124[0...n] Field current for motor flux 20 % / I_field flux 20%
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 14.7 [%]
p50125[0...n] Field current for motor flux 25 % / I_field flux 25%
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 18.4 [%]
p50126[0...n] Field current for motor flux 30 % / I_field flux 30%
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 22.0 [%]
p50127[0...n] Field current for motor flux 35 % / I_field flux 35%
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 25.7 [%]