EasyManua.ls Logo

Siemens SINAMICS DCM - Band-Stop 2 Quality; Band-St 2 Quality; CI: Lead;Lag Element Signal Source; Lead;Lag Elem S_S; Derivative-Action Element Derivative-Action Time; D-Act el T_D-Act; Derivative-Action Element Smoothing Time; Der-Act el T_Dae

Siemens SINAMICS DCM
1204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
421
2 Parameters
2.2 List of parameters
Dependency: Refer to: p50204, p50629, r52178
Description: Sets the quality for band-stop 2.
Value: 0: Quality = 0.5
1: Quality = 1
2: Quality = 2
3: Quality = 3
Dependency: Refer to: p50203, p50629, r52178
Description: Sets the derivative-action time for the derivative-action element.
Dependency: Refer to: p50206, p50627, r52168, r52169
Description: Sets the smoothing time for the derivative-action element.
Dependency: Refer to: p50205, p50627, r52168, r52169
Description: Sets the signal source for the lead/lag element.
Dependency: Refer to: p50208, p50209, r52156
p50204[0...n] Band-stop 2 quality / Band-st 2 quality
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
p50205[0...n] Derivative-action element derivative-action time / D-act el t_d-act
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 0 [ms]
p50206[0...n] Derivative-action element smoothing time / Der-act el t_DAE
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 100 [ms] 0 [ms]
p50207 CI: Lead/lag element signal source / Lead/lag elem S_s
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 52179[0]