2 Parameters
2.2 List of parameters
SINAMICS DCM
478 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the amplitude for the frequency response plot for the optimization run "Speed control optimization for drives that
are capable of oscillation" (p50051 = 29).
Description: Sets the time for the frequency response plot for the optimization run "Speed control optimization for drives that are
capable of oscillation" (p50051 = 29).
In this case, an average is generated over the time set here per measuring frequency.
Note: High values improve the result, however they slow down the measuring time.
For the 3.0 s setting, it takes approximately 9 minutes to plot the frequency response.
Description: Sets the input quantity for armature current controller adaptation.
Value: 0: Ia_act r52117
1: Ia_set r52119
Dependency: Refer to: p50571, p50572
Description: Setting to activate the adaptation of non-linear inductances for the armature current controller.
Value: 0: Adaptation non-linear L active
1: Fixed value 100 % effective
Dependency: Refer to: p50570, p50572, r52350
p50566 Speed controller optimization frequency response plot amplitude / f_plot amplitude
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2660
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.01 [%] 5.00 [%] 1.00 [%]
p50567 Speed controller optimization frequency response plot time / f_plot time
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2660
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.30 [s] 3.00 [s] 1.00 [s]
p50570[0...n] Adaptation armature current controller changeover input / Adapt Ia chgov inp
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6853
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50571[0...n] Adaptation armature current controller non-linear L activation / Adapt N_lin L act
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6853
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0