SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
429
2 Parameters
2.2 List of parameters
Description: Sets activation/de-activation of the integral component on the field current controller.
Value: 0: Deactivated
1: Activated
Dependency: Refer to: p50255, p50256
Note: If value = 0:
The integral component of the field current controller is kept constantly at zero (i.e. the field current controller
functions solely as a proportional controller).
Description: Sets the P gain of the field current controller.
Dependency: Refer to: p50256
Note: The parameter is set automatically during the optimization run for closed-loop field current control (p50051 = 24).
Description: Sets the integral time of the field current controller.
Dependency: Refer to: p50255
Note: The parameter is set automatically during the optimization run for closed-loop field current control (p50051 = 24).
Description: Sets the standstill field for closed-loop field current control.
Dependency: Refer to: p50692
Note: The field current is reduced to this value when the "Automatic field current reduction" function is parameterized
(p50082 = 2) or in the case of signal-driven selection of the ""Standstill excitation" function (p50692).
p50254[0...n] Field current controller integral component activation / I_field_ctr I comp
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 1
p50255[0...n] Field current controller P gain / I_field ctr Kp
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6908
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.01 100.00 5.00
p50256[0...n] Field current controller integral time / I_field ctr Tn
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6908
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.001 [s] 10.000 [s] 0.200 [s]
p50257[0...n] Closed-loop field current control standstill field / If_ctr stst_field
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 0.0 [%]