Siemens SINAMICS DCM - Field Power Unit Operating Mode; Field PU Op Mode

Siemens SINAMICS DCM
1204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCM
392 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the operating mode for the field power unit.
If p50082 = 1, 2, 3, 4, the motor flux is calculated according to the field characteristic (p50120 to p50139) as a
function of the field current actual value (r52265).
Value: 0: No field
1: Field switched with line contactor
2: Standstill field for >= o7.0
3: Field continuously active
4: Field switched with Auxiliaries ON signal
21: External field power unit, otherwise as setting 1
22: External field power unit, otherwise as setting 2
23: External field power unit, otherwise as setting 3
24: External field power unit, otherwise as setting 4
Dependency: Refer to: r50073, p50076, p50258, p50265, p50612, p51838, r52265, r52268, r52290
Notice: Although it is permissible for the parameter to be changed to values not equal to 0 in operating states o1.0, such
changes will not be applied until operating states greater than or equal to o7.0.
Note: If an external field device is used, the setpoint comes from r52268 (e.g. via an analog output or over the peer-to-peer
interface).
The rated direct current of the external field device should be set in p51838. This value is also displayed in r50073[1].
p50076[2] is redundant.
If the external field device sends a field current actual value signal, this should be fed in via p50612. If the external
field device is not able to send a field current actual value signal, p50263 should be set to a value of 1 or 2.
If the external field device sends an I_field < I_field_min signal, this can be fed in at injection point p50265.
If p50082 = 0:
- No field is used (e.g. in the case of permanent-magnet motors). The field firing pulses are disabled. The motor flux
is set to the value for 100% rated flux.
If p50082 = 1:
- Internal field power unit. The line supplies for the field and armature sections are connected or disconnected
simultaneously. The field firing pulses are enabled/disabled at the same time as the line contactor closes/opens; the
field current decays with the field time constant during freewheeling.
If p50082 = 2:
- Internal field power unit. Automatic injection of standstill field set in p50257 after expiry of a period of time set in
p50258 once operating state o7 or higher has been reached.
If p50082 = 3:
- Internal field power unit. The field is active continuously.
If p50082 = 4:
- Internal field power unit. The field is switched together with the Auxiliaries ON signal (p53210.2).
If p50082 = 21:
- External field device. The field is controlled in the same way as with p50082 = 1.
If p50082 = 22:
- External field device. The field is controlled in the same way as with p50082 = 2.
If p50082 = 23:
- External field device. The field is controlled in the same way as with p50082 = 3.
If p50082 = 24:
- External field device. The field is controlled in the same way as with p50082 = 4.
p50082 Field power unit operating mode / Field PU op mode
DC_CTRL Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: 6910, 8044,
8047
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 24 2