2 Parameters
2.2 List of parameters
SINAMICS DCM
126 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Displays the receive errors at the commissioning interface (RS232).
Index: [0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
Description: Sets the baud rate for the fieldbus interface USS.
Value: 4: 2400 baud
5: 4800 baud
6: 9600 baud
7: 19200 baud
8: 38400 baud
9: 57600 baud
10: 76800 baud
11: 93750 baud
12: 115200 baud
13: 187500 baud
Note: Fieldbus IF: Fieldbus interface
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected.
Description: Sets the address for the fieldbus interface USS.
Dependency: Refer to: p2030
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected.
r2019[0...7] Comm IF error statistics / Comm err
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p2020 Field bus interface baud rate / Field bus baud
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 9310
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
4 13 8
p2021 Field bus interface address / Field bus address
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 31 0