EasyManua.ls Logo

Siemens SINAMICS DCM - Mast;Sl Drive Ctr Speed Controller Tracking I Component; Set Speed Controller Integral Component Duration; Set I_Comp Dur; Speed Controller Speed Setpoint Smoothing Time Constant

Siemens SINAMICS DCM
1204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
425
2 Parameters
2.2 List of parameters
Notice: - For the droop, generally values up to 10 % are practical (p50227 = 0.000 ... 0.100). Under certain circumstances,
higher values can result in an unstable response of the speed controller.
- The droop is entered as absolute factor without any dimensions and it is especially important to note that it is not a
percentage.
Example:
Set droop = 5 % --> p50227 = 0.05
Note: The adaptation of the droop is defined using 2 pairs of values.
Pair of values 1:
p50558/p50552 (x/y coordinate)
Pair of values 2:
p50561/p50227 (x/y coordinate)
Description: Sets the smoothing time constant for smoothing the speed setpoint on the speed controller.
Recommendation: If the ramp-function generator is being used, setting lower values may be sensible.
Note: The value is set automatically during the optimization run for the speed controller to the same value as the integral
time (Tn) (p50051 = 26).
Description: Setting for the control of the integral component tracking on the speed controller.
Value: 0: Tracking ON
1: Tracking OFF
Dependency: Refer to: p50084, p50687
Note: p50229 = 0:
Tracking of the integral component on the speed controller activated. The speed actual value is used as speed
setpoint and the integral component of the speed controller is tracked so that r52148 = r52140 results.
p50229 = 1:
Tracking of the integral component on the speed controller de-activated.
Description: Sets the duration for setting the integral component on the speed controller.
Following a positive edge on binector input p50695, the integral component of the speed controller is set to the value
of the signal source set at connector input p50631.
p50228[0...n] Speed controller speed setpoint smoothing time constant / n_ctr n_set T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50229[0...n] Mast/Sl drive ctr speed controller tracking I component / M/S drve ctr track
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50230[0...n] Set speed controller integral component duration / Set I_comp dur
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6815
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]

Table of Contents

Other manuals for Siemens SINAMICS DCM

Related product manuals