2 Parameters
2.2 List of parameters
SINAMICS DCM
258 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Displays the required memory in bytes for the actual parameterization.
This applies, if the trace for the measurement functions is used.
Index: [0] = Trace 0
[1] = Trace 1
Dependency: Refer to: r4799
Description: Sets the trigger condition for the trace.
Value: 1: Immediate trace start
2: Positive edge
3: Negative edge
4: Entry to hysteresis band
5: Leaving hysteresis band
6: Trigger at bit mask
7: Start with function generator
8: Trigger at bit mask with edge
Index: [0] = Trace 0
[1] = Trace 1
Description: Selects the trigger signal for the trace.
Index: [0] = Trace 0 parameter in BICO format
[1] = Trace 1 parameter in BICO format
[2] = Trace 0 PINx with DO Id and chart Id
[3] = Trace 0 PINx with block Id and PIN Id
[4] = Trace 1 PINy with DO Id and chart Id
[5] = Trace 1 PINy with block Id and PIN Id
Dependency: Only effective when p4710 does not equal 1.
Note: It only makes sense to trace the PINs using the commissioning software.
For index 2(4) and 3(5) equal to zero, index 0(1) can only be written and vice versa.
Re index 0 ... 1:
Here, the trigger signal for trace 0 or 1 is entered as parameter in the BICO format.
For trace with a physical address (p4789), the data type of the trigger signal is set here.
r4709[0...1] Trace memory space required for measuring functions / Trace mem required
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - -
p4710[0...1] Trace trigger condition / Trace Trig_cond
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
1 8 2
p4711[0...5] Trace trigger signal / Trace trig_signal
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - 0