SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
249
2 Parameters
2.2 List of parameters
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency: Refer to: p4102, p4103, r4104, r4105
Note: The following applies for a corresponding alarm:
- Remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value (p4102[2x] -
hysteresis (p4118[x]).
The following applies for a corresponding fault:
- Remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value (p4102[2x+1]) -
hysteresis (p4118[x]) and the fault has been acknowledged.
Description: Setting to activate/deactivate the filter to smooth the temperature signal for the Terminal Module 150 (TM150).
The smoothing is realized with a 1st order lowpass filter
The effective smoothing time constant depends on the number of channels that are simultaneously active and is
displayed in r4120.
Value: 0: Filter deactivated
1: Filter activated
Index: [0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency: Refer to: r4120
Description: Displays the smoothing time constant for the temperature filter for Terminal Module 150 (TM150).
Dependency: Refer to: r4105, p4111, r4112, r4113
Note: The time constant lies in the range from 80 to 1000 ms and depends on the number of channels that are
simultaneously active.
p4119[0...11] TM150 activate/deactivate smoothing / TM150 smooth act
TM150 Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: 9626, 9627
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r4120 TM150 temperature filter time constant / TM150 temp_filt T
TM150 Can be changed: - Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: 9626, 9627
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [ms] - [ms] - [ms]