2 Parameters
2.2 List of parameters
Description: Displays the IP address of the second PROFINET controller connected with the device via CBE20/CBE25.
Description: Data setting to read topology properties.
The result is displayed depending on the property in r9207 or r9208.
Re index 0:
0: actual topology, 1: target topology
Re index 1:
Sets the component number of the component involved.
Re index 2:
7: Name (r9208)
8: Component type (r9207)
9: Number of DRIVE-CLiQ connections (r9207)
11: Manufacturer (upper byte) and version (lower byte) (r9207)
12: Serial number (r9208)
13: Index (r9207)
15: Comparison level (r9207)
23: Order number (r9207)
24: Hardware serial number (r9208)
25: Collective order number (r9207)
28: Firmware version (r9207)
29: EEPROM version (r9207)
30: Hardware version (r9207)
1000: Name of DRIVE-CLiQ connection 0 (r9208)
1001: Name of DRIVE-CLiQ connection 1 (r9208)
...
1015: Name of DRIVE-CLiQ connection 15 (r9208)
Index: [0] = Actual topology/target topology
[1] = Component number
[2] = Identifier/property
Dependency: Refer to: r9207, r9208
r8972[0...3] CBE2x IP Address Remote Controller 2 / CBE2x IP Rem Ctrl2
CU_DC (PROFINET
CBE20), CU_DC_R
(PROFINET CBE20),
CU_DC_R_S
(PROFINET CBE20),
CU_DC_S
(PROFINET CBE20)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 -
p9206[0...2] Topology direct access / Topo access
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Topology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4294967295 0