2 Parameters
2.2 List of parameters
SINAMICS DCM
384 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Displays more detailed information about faults which have occurred with numbers 60000 and higher.
[0] = Fault value
[1] = Additional information about the most recent fault which occurred (see corresponding fault)
...
[30] = Additional information about the most recent fault which occurred (see corresponding fault)
[31] = Fault number
Description: Setting to select the optimization run for the next ON command.
Value: 0: No optimization run
23: Armature current control (for inductive loads)
24: Closed-loop field current control
25: Closed-loop armature current control
26: Closed-loop speed control and moment of inertia
27: Field weakening control
28: Friction compensation
29: Torsion optimization
30: CCP (Converter Commutation Protector)
Notice: If value = 30:
The CCP optimization run does not require a switch-on command and is directly started when selecting the value.
Note: Only a value of 0 can be set at the right-hand CUD.
A value not equal to 0 can only be set in the operating states o7.0 and o7.1 if an optimization run is presently not
active.
If value = 0:
No optimization run has been selected.
If value = 23:
Optimization run for pre-control and the current controller for the armature converter (for inductive loads).
If value = 24:
Optimization run for pre-control and the current controller for the field converter.
If value = 25:
Optimization run for pre-control and the current controller for the armature converter.
If value = 26:
Optimization run for the speed controller and moment of inertia.
If value = 27:
Optimization run for field weakening.
If value = 28:
Optimization run for friction compensation.
If value = 29:
Optimization run for speed controllers and moment of inertia for drives that are capable of oscillation.
If value = 30:
Optimization run for CCP (Converter Commutation Protector).
r50047[0...31] Faults additional information / Fault add info
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2651
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p50051 Optimization run selection / Opt run sel
DC_CTRL Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: 2660
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 30 0

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals