EasyManua.ls Logo

Siemens SINAMICS DCM - Faults Additional Information; Fault Add Info; Optimization Run Selection; Opt Run Sel

Siemens SINAMICS DCM
1204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCM
384 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Displays more detailed information about faults which have occurred with numbers 60000 and higher.
[0] = Fault value
[1] = Additional information about the most recent fault which occurred (see corresponding fault)
...
[30] = Additional information about the most recent fault which occurred (see corresponding fault)
[31] = Fault number
Description: Setting to select the optimization run for the next ON command.
Value: 0: No optimization run
23: Armature current control (for inductive loads)
24: Closed-loop field current control
25: Closed-loop armature current control
26: Closed-loop speed control and moment of inertia
27: Field weakening control
28: Friction compensation
29: Torsion optimization
30: CCP (Converter Commutation Protector)
Notice: If value = 30:
The CCP optimization run does not require a switch-on command and is directly started when selecting the value.
Note: Only a value of 0 can be set at the right-hand CUD.
A value not equal to 0 can only be set in the operating states o7.0 and o7.1 if an optimization run is presently not
active.
If value = 0:
No optimization run has been selected.
If value = 23:
Optimization run for pre-control and the current controller for the armature converter (for inductive loads).
If value = 24:
Optimization run for pre-control and the current controller for the field converter.
If value = 25:
Optimization run for pre-control and the current controller for the armature converter.
If value = 26:
Optimization run for the speed controller and moment of inertia.
If value = 27:
Optimization run for field weakening.
If value = 28:
Optimization run for friction compensation.
If value = 29:
Optimization run for speed controllers and moment of inertia for drives that are capable of oscillation.
If value = 30:
Optimization run for CCP (Converter Commutation Protector).
r50047[0...31] Faults additional information / Fault add info
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2651
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p50051 Optimization run selection / Opt run sel
DC_CTRL Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: 2660
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 30 0

Table of Contents

Other manuals for Siemens SINAMICS DCM

Related product manuals