2 Parameters
2.2 List of parameters
SINAMICS DCM
420 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the signal source for EMF actual value or armature voltage actual value for armature current pre-control.
If p50162[D] = 2: Armature voltage actual value
If p50162[D] = 3: EMF actual value
Description: Sets the smoothing time constant for smoothing the speed actual value on the speed controller.
Description: Sets the resonant frequency for band-stop 1.
Dependency: Refer to: p50202, p50628, r52177
Description: Sets the quality for band-stop 1.
Value: 0: Quality = 0.5
1: Quality = 1
2: Quality = 2
3: Quality = 3
Dependency: Refer to: p50201, p50628, r52177
Description: Sets the resonant frequency for band-stop 2.
p50193 CI: EMF/Ua external signal source / EMF/Ua ext sig s
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 6852
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 52287[0]
p50200[0...n] Speed controller speed actual value smoothing time constant / n_ctr n_act T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50201[0...n] Band-stop 1 resonant frequency / Band-st 1 f_n
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 [Hz] 140 [Hz] 1 [Hz]
p50202[0...n] Band-stop 1 quality / Band-st 1 quality
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
p50203[0...n] Band-stop 2 resonant frequency / Band-st 2 f_n
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6810
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 [Hz] 140 [Hz] 1 [Hz]