SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
503
2 Parameters
2.2 List of parameters
The value indicates the percentage value for the mapping of an input voltage of 10 V or an input current of 20 mA at
the analog input.
Example:
p50711 = 90%
--> 10 V or 20 mA is scaled to 90%
--> 5 V or 10 mA is equivalent to 45%
Description: Sets the offset for analog input 1 (X177.27/28) on the CUD.
Description: Sets the signal processing mode for analog input 1 (X177.27/28) on the CUD.
Value: 0: Signal not controlled
1: Signal absolute value generation
2: Signal inverted
3: Signal absolute value generation inverted
Description: Sets the signal source for inverting the signal from analog input 1 (X177.27/28) on the CUD.
1 signal: Inversion
0 signal: No inversion
Description: Sets the time constant for smoothing the signal from analog input 1 (X177.27/28) on the CUD.
p50712 CUD analog input 1 offset / CUD AI 1 offs
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2080
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
p50713 CUD analog input 1 signal processing / CUD AI 1 sig proc
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 2080
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
p50714 BI: CUD analog input 1 inversion / CUD AI 1 inv
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2080
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p50715 CUD analog input 1 smoothing time constant / CUD AI 1 T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2080
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]