2 Parameters
2.2 List of parameters
Description: Sets positive setpoint limiting after the ramp-function generator.
Description: Sets negative setpoint limiting after the ramp-function generator.
Description: Sets the operating mode for the ramp-up integrator.
The ramp-up integrator controls the changing over of the ramp-function generator parameter sets as appropriate for
the set operating mode once the setpoint has been reached for the first time.
Value: 0: RFG normal operation
1: Operating mode 1
2: Operating mode 2
3: Operating mode 3
Note: If p50302 = 0:
- The parameter sets are not changed over and ramp-function generator setting 1 is always used (or the setting made
using p50637, p50638).
If p50302 = 1:
- Once the setpoint has been reached for the first time, the ramp-function generator parameter set is changed over
from 1 to 0.
If p50302 = 2:
- Once the setpoint has been reached for the first time, the ramp-function generator parameter set is changed over
from 1 to 2.
If p50302 = 3:
- Once the setpoint has been reached for the first time, the ramp-function generator parameter set is changed over
from 1 to 3.
Description: Sets the ramp-up time for ramp-function generator parameter set 1.
p50300[0...n] RFG positive setpoint limit after ramp-function generator / RFG pos after RFG
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3155
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p50301[0...n] RFG negative setpoint limit after ramp-function generator / RFG neg after RFG
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3155
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p50302[0...n] RFG ramp-up integrator operating mode / RFG integ op mode
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 3150
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
p50303[0...n] RFG ramp-up time 1 / RFG t_ramp-up 1
DC_CTRL Can be changed: C2(1), U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3150
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [s] 650.00 [s] 10.00 [s]