SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
95
2 Parameters
2.2 List of parameters
Notice: When changing over from one technological unit into another, or when changing the reference parameter, a
changeover is not made.
Description: Sets the sensor type for the motor temperature monitoring.
Value: 0: No sensor
2: KTY84
Dependency: Refer to: r0458
Description: Runs the corresponding macro files.
The binector inputs of the corresponding command data set are appropriately interconnected.
The selected macro file must be available on the memory card/device memory.
Example:
p0700 = 6 --> macro file PM000006.ACX is run.
Dependency: Refer to: p0015, p1000, p1500, r8571
Notice: No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note: The macros in the specified directory are displayed in r8571. r8571 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
BI: Binector Input
CDS: Command Data Set
Description: Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0700 = 6 --> macro file PM000006.ACX is run.
Dependency: Refer to: r8571
Notice: No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
p0601[0...n] Motor temperature sensor type / Mot_temp_sens type
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: MDS Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0
p0700[0...n] Macro Binector Input (BI) / Macro BI
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: CDS, p0170 Func. diagram: -
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 999999 0
p0700 Macro Binector Input (BI) for TMs / Macro BI TM
TM15DI_DO, TM31 Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 999999 0