2 Parameters
2.2 List of parameters
SINAMICS DCM
430 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the delay time for automatic field current reduction.
Description: Sets the smoothing time constant for the setpoint for field current pre-control.
Dependency: Refer to: p50261
Note: This smoothing enables field-current pre-control to be decoupled from the field current controller.
Description: Sets the smoothing time constant for the setpoint for the field current controller.
Dependency: Refer to: p50260
Note: This smoothing enables field-current pre-control to be decoupled from the field current controller.
Description: Selection of the input variable for determining the motor flux.
Value: 0: Field current controller actual value (r52265)
1: EMF pre-control output (r52293 or r52268)
2: Field current controller setpoint (r52268)
Note: If value = 0:
This setting is recommended for a fully compensated DC motor.
If value = 1:
This setting is recommended for an uncompensated DC motor. The EMF controller must be active for this setting (the
EMF controller compensates the armature reaction).
If value = 2:
This setting is recommended for a fully compensated DC motor.
p50258[0...n] Cl-loop field current control field current reduction delay time / If_ctr I_red t_del
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 60.0 [s] 10.0 [s]
p50260[0...n] Field current pre-control setpoint smoothing time constant / Field_prec set T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50261[0...n] Field current controller setpoint smoothing time constant / I_field_ctr set T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50263[0...n] Selection of motor flux input variable / Mot fl input sel
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1