2 Parameters
2.2 List of parameters
SINAMICS DCM
512 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the signal source for the output value at analog output 1 (X177.51/52).
Note: AO: Analog Output
Description: Sets the mode for signal processing at analog output 1 (X177.51/52).
Value: 0: Signal not controlled
1: Signal absolute value generation
2: Signal inverted
3: Signal absolute value generation inverted
Description: Sets the time constant for smoothing the signal from analog output 1 (X177.51/52).
Description: Sets the scaling for analog output 1 (X177.51/52).
The value indicates the output value for the mapping of an input value of 100% at the analog output.
Note: Example:
p50758 = 5 V
--> 100% is scaled to 5 V
--> 50% corresponds to 2.5 V
p50755 CI: CUD analog output 1 signal source / CUD AO 1 sig s
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 2095
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0
p50756 CUD analog output 1 signal processing / CUD AO 1 sig proc
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 2095
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
p50757 CUD analog output 1 smoothing time constant / CUD AO 1 T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2095
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50758 CUD analog output 1 scaling / CUD AO 1 scal
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2095
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-200.00 [V] 200.00 [V] 10.00 [V]