EasyManua.ls Logo

Siemens SINAMICS DCM - Messages for Field Current Threshold Minimum Hysteresis; Messages for Field Current Threshold Minimum Threshold; Messages for Setpoint;Actual Value Deviation 1 Hysteresis; Messages for Setpoint;Actual Value Deviation 1 off Delay

Siemens SINAMICS DCM
1204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCM
450 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the hysteresis for the "Setpoint/actual value deviation 1 reached" message.
The message is triggered when the threshold is overshot.
Once the value falls below the threshold minus the hysteresis, the message is withdrawn.
Dependency: Refer to: p50388, p50390, p50590, p50591, r53025
Refer to: F60031
Description: Sets the OFF delay for the "Setpoint/actual value deviation 1 reached" message.
Dependency: Refer to: p50388, p50389, p50590, p50591, r53025
Refer to: F60031
Description: Sets the threshold for the "Field current threshold minimum" message.
Dependency: Refer to: p50395, r53026
Note: This threshold also affects the phase logic execution in the context of the Direction reversal by field reversal and
Braking by field reversal functions.
The "Field current threshold minimum" message is displayed via r53026.0.
Description: Sets the hysteresis for the "Field current threshold minimum" message.
The message is triggered when the threshold is undershot.
Once the value rises above the threshold plus the hysteresis, the message is withdrawn.
Dependency: Refer to: r53026
Note: The "Field current threshold minimum" message is displayed via r53026.0.
p50389[0...n] Messages for setpoint/actual value deviation 1 hysteresis / Set/act 1 hyst
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8020
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 200.00 [%] 1.00 [%]
p50390[0...n] Messages for setpoint/actual value deviation 1 OFF delay / Set/act t_OFF
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8020
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 100.0 [s] 3.0 [s]
p50394[0...n] Messages for field current threshold minimum threshold / Msg If min thresh
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8025
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 200.00 [%] 3.00 [%]
p50395[0...n] Messages for field current threshold minimum hysteresis / Msg If min hyst
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8025
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 100.00 [%] 1.00 [%]

Table of Contents

Other manuals for Siemens SINAMICS DCM

Related product manuals