SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
105
2 Parameters
2.2 List of parameters
Note: Re bits 00, 01, 02, 04, 05, 06, 09:
For PROFIdrive, these signals are used for status word 1.
Description: Sets the PROFIBUS address for PROFIBUS interface (X126) on the Control Unit.
The address can be set as follows:
Via p0918
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note: Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
Description: Sets the PROFIBUS address for PROFIBUS interface (X126) on the Control Unit.
The address can be set as follows:
Via p0918
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note: Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
Description: Sets the send and receive telegram.
Value: 390: SIEMENS telegram 390, PZD-2/2
999: Free telegram configuration with BICO
08 Controller enable Yes No -
09 Control request Yes No -
11 Pulses enabled Yes No -
12 Open holding brake Yes No -
13 Command close holding brake Yes No -
14 Pulse enable from the brake control Yes No -
15 Setpoint enable from the brake control Yes No -
p0918 PROFIBUS address / PB address
CU_DC_R,
CU_DC_R_S
Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 1520, 2410
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 126 125
p0918 PROFIBUS address / PB address
CU_DC, CU_DC_S Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 1520, 2410
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 126 126
p0922 IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: 1520, 2420
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
390 999 999