2 Parameters
2.2 List of parameters
SINAMICS DCM
286 List Manual (LH8), 02/2015, 6RX1800-0ED76
Note: OA: Open Architecture (OA application)
Description: Displays the total length of the IDs of all the invalid OA applications installed on the memory card/device memory.
Dependency: Refer to: r4975, r4978, r4979
Note: The identifier of an invalid OA application comprises a maximum of 8 characters plus separator.
Description: Displays the IDs of all the invalid OA applications installed on the memory card/device memory.
r4978[0...8]: Identifier of invalid OA application 1
r4978[9...17]: Identifier of invalid OA application 2, ...
Dependency: Refer to: r4975, r4976, r4979
Notice: If there is no invalid OA application, then it is not possible to access an index.
Description: Displays the error code of the invalid OA applications installed on the memory card/device memory.
r4979[0]: Fault value of OA application 1
r4979[1]: Fault value of OA application 2, ...
Dependency: Refer to: r4975, r4976, r4978
Notice: If there is no invalid OA application, then it is not possible to access an index.
Note: The value in the error code must be interpreted in binary form. The bits have the following meaning:
Bit 0: Incompatible OA interface version.
Bit 1: OA application could not be loaded.
Bit 2: Incorrect description files.
Bit 3: OA application does not define a CPU type.
Bit 4: OA application for this device not supported (incorrect CPU type).
Bit 5: OA application for this device not supported (incorrect type ID).
Bit 6: Incorrect description files (Const/Startup incompatible).
r4976 OA invalid identifier total length / OA inv ID tot_lgth
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: OEM range Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r4978[0...n] OA invalid identifier / OA inv ID
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned8 Dyn. index: r4976 Func. diagram: -
P-Group: OEM range Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r4979[0...n] OA invalid error code / OA inv error code
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: r4975 Func. diagram: -
P-Group: OEM range Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -

Table of Contents