F60058 Parameter settings not consistent
Message value: %1
Message class: General drive fault (19)
Drive object: DC_CTRL
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: Inconsistent values have been set in parameters depending on each other.
Fault value (r0949, interpret decimal):
0: Field weakening active (p50081 = 1) is not permissible when the EMF is used as speed setpoint (p50083 = 3).
1: Thyristor blocking voltage calculation active (p50166 = 1) for line frequencies > 65 Hz (p50364) is not permissible.
2: Setting of p51799 does not match the setting of p51800, p51802 and p51803.
3: For a line frequency > 65 Hz, p51800 must be < 10.
4: Setting of p50075 does not match the setting of p51799 (dynamic overload capability not permissible for single-
phase operation).
5: Single-phase operation (p51799 = 1) not permissible for this device type.
6: Thyristor blocking voltage calculation (p50166 = 1) not possible for this device.
7: If p50083[D] = 2, p0400[0] = 0 is not permissible and if p50083[D] = 5, p0400[1] = 0 is not permissible.
8: For p50830 > 0, p51800 > 1 is not permissible , except 11 and 21 (thyristor diagnostics is only permissible for a
single drive and for a parallel master).
9: For p50075 = 0, p50067 > 1 is not permissible.
10: Line frequency > 120 Hz is not permissible for this power unit (p50364).
11: For a 12-pulse parallel connection, p50153 = 2 is not permissible.
Remedy: Make the setting as appropriate for the fault value displayed.
F60061 Thyristor test unsuccessful
Message value: %1
Message class: Power electronics faulted (5)
Drive object: DC_CTRL
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: With the thyristor test activated (p50830), a fault was detected for at least one thyristor.
Fault value (r0949, interpret decimal):
1: Thyristor defective (V11 and/or V24)
2: Thyristor defective (V12 and/or V25)
3: Thyristor defective (V13 and/or V26)
4: Thyristor defective (V14 and/or V21)
5: Thyristor defective (V15 and/or V22)
6: Thyristor defective (V16 and/or V23)
8: Ground fault in the armature circuit
11: Thyristor cannot be fired (V11)
12: Thyristor cannot be fired (V12)
13: Thyristor cannot be fired (V13)
14: Thyristor cannot be fired (V14)
15: Thyristor cannot be fired (V15)
16: Thyristor cannot be fired (V16)
17: Two or more thyristors from V11 ... V16 cannot be fired
21: Thyristor cannot be fired (V21)
22: Thyristor cannot be fired (V22)
23: Thyristor cannot be fired (V23)
24: Thyristor cannot be fired (V24)
25: Thyristor cannot be fired (V25)
26: Thyristor cannot be fired (V26)
27: Two or more thyristors from V21 ... V26 cannot be fired
31: Thyristor cannot block (V11 or V21)
32: Thyristor cannot block (V12 or V22)