2 Parameters
2.2 List of parameters
SINAMICS DCM
510 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the time constant for smoothing the signal from the "main actual value" analog input (XT1.103/104).
Description: Sets the signal source for enabling the analog input for the "main actual value (XT1.103/104).
Note: 1 signal: Analog input enabled
0 signal: Analog input not enabled (r52013 = 0%).
Description: Sets the setpoint for the simulation of the "main actual value" analog input (XT1.103/104).
Dependency: Refer to: p50749
Note: Simulation is selected using p50749 = 1.
Description: Setting to select the simulation of the "main actual value" analog input (XT1.103/104).
Value: 0: Simulation deactivated
1: Simulation activated
Dependency: Refer to: p50747
Note: The setpoint for the simulation is set in p50747.
Description: Sets the signal source for the output value at analog output 0 (X177.49/50).
p50745 Analog input main actual value smoothing time constant / AI m act T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p50746 BI: Signal source to enable analog input main actual value / AI m act ena sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p50747 Analog input main actual value setpoint simulation / AI m_actV sim setp
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-130.0 [%] 130.0 [%] 0.0 [%]
p50749 Analog input main actual value simulation selection / AI m_actV sim sel
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50750 CI: CUD analog output 0 signal source / CUD AO 0 sig s
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 2095
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0