2 Parameters
2.2 List of parameters
SINAMICS DCM
252 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Display and binector output to reset XIST1_ERW.
Dependency: Refer to: p4652, r4653, p4655
Note: The reset of XIST1_ERW is initiated via binector input p4655.
Binector output r4654 is reset with a 0 signal from binector input p4655.
Description: Sets the signal source to reset XIST1_ERW (CO: r4653).
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = -
Dependency: Refer to: p4652, r4653, r4654
Note: The reset of XIST1_ERW depends on the selected mode (p4652).
Description: Sets the filter bandwidth for Sensor Module SMx10 (resolver) and SMx20 (sin/cos).
The value set on the Sensor Module is displayed in r4661.
The Sensor Module hardware only supports the following values:
- 0: The Sensor Module's default is used.
- 50 kHz
- 170 kHz
- 500 kHz
- Unlimited: Only the bandwidth of the operational amplifier is effective.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Reserved
Dependency: Refer to: r4661
Note: A value of zero is displayed if an encoder is not present.
r4654.0...8 CO/BO: XIST1_ERW status / XIST1_ERW stat
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 4750
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Encoder 1 XIST1_ERW reset High Low -
08 Encoder 2 XIST1_ERW reset High Low -
p4655[0...2] BI: XIST1_ERW reset signal source / XIST1_ERW resS_src
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 4750
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4660[0...2] Sensor Module filter bandwidth / SM Filt_bandw
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: C2(4) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [kHz] 20000.00 [kHz] 0.00 [kHz]