SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
433
2 Parameters
2.2 List of parameters
Value: 0: Deactivated
1: Activated
Dependency: Refer to: p50284
Note: If value = 0:
The integral component of the EMF controller is kept constantly at zero (i.e. the EMF controller functions solely as a
proportional controller).
Description: Sets the P gain of the EMF controller.
Dependency: Refer to: p50276
Note: The parameter is set automatically during the optimization run for field weakening (p50051 = 27).
Description: Sets the integral time of the EMF controller.
Dependency: Refer to: p50275
Note: The parameter is set automatically during the optimization run for field weakening (p50051 = 27).
Description: Sets the value for the EMF controller's droop feedback.
Note: If value = 0:
Droop feedback is de-activated.
Description: Sets the smoothing time constant for the setpoint for EMF controller pre-control.
Dependency: Refer to: p50283
Note: This smoothing enables the EMF controller pre-control to be decoupled from the EMF controller.
p50275[0...n] EMF controller P gain / EMF ctr Kp
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.01 100.00 0.60
p50276[0...n] EMF controller integral time / EMF ctr Tn
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.010 [s] 10.000 [s] 0.200 [s]
p50277[0...n] EMF controller droop / EMF ctr droop
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 10.0 [%] 0.0 [%]
p50280[0...n] EMF controller pre-control setpoint smoothing time constant / EMF prec set T
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals