SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
1087
4 Faults and alarms
4.2 List of faults and alarms
16 (= 10 hex):
The receive telegram is too early.
32 (= 20 hex):
Error in the telegram header.
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
64 (= 40 hex):
Timeout in the telegram send list.
65 (= 41 hex):
Telegram type does not match send list.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
F33875 (N, A) Encoder 3 DRIVE-CLiQ (CU): Supply voltage failed
Message value: Component number: %1, fault cause: %2
Message class: Supply voltage fault (undervoltage) (3)
Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the
supply voltage has failed.
Fault cause:
9 (= 09 hex):
The power supply voltage for the components has failed.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - carry out a POWER ON (power off/on).
- check the power supply voltage wiring for the DRIVE-CLiQ component (interrupted cable, contacts, ...).
- check the dimensioning of the power supply for the DRIVE-CLiQ component.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F33912 Encoder 3: Device combination is not permissible
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction: OFF1 (IASC/DCBRK, NONE)
Acknowledge: PULSE INHIBIT
Cause: The selected device combination is not supported.