2 Parameters
2.2 List of parameters
SINAMICS DCM
84 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Displays the identification/serial number of encoder 1.
Index 0 = first character of the identification number
...
Index x = 20 hex (blank) --> separation between the identification number of serial number
Index x + 1 = 2F hex (slash) --> separation between the identification number of serial number
Index x + 2 = 20 hex (blank) --> separation between the identification number of serial number
Index x + 3 = first character of the serial number
...
Index y with contents = last character of the serial number
Dependency: Refer to: r0460, r0461, r0462, r0463, r0464
Notice: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
Note: The individual characters of the identification number/serial number are available coded as ASCII characters.
Description: Displays the identification/serial number of encoder 2.
Index 0 = first character of the identification number
...
Index x = 20 hex (blank) --> separation between the identification number of serial number
Index x + 1 = 2F hex (slash) --> separation between the identification number of serial number
Index x + 2 = 20 hex (blank) --> separation between the identification number of serial number
Index x + 3 = first character of the serial number
...
Index y with contents = last character of the serial number
Dependency: Refer to: r0460, r0461, r0462, r0463, r0464
Notice: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
Note: The individual characters of the identification number/serial number are available coded as ASCII characters.
Description: Displays the resolution of the absolute position for a linear absolute encoder.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency: Refer to: p0422
r0465[0...27] Encoder 1 identification number/serial number / Enc1 ID_no/Ser_no
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r0466[0...27] Encoder 2 identification number/serial number / Enc2 ID_no/Ser_no
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r0469[0...2] Absolute encoder linear measuring step / Enc lin meas step
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [nm] - [nm] - [nm]