EasyManua.ls Logo

Siemens SINAMICS DCM - DRIVE-Cliq Component Parameter Index; DQ Para_Index; DRIVE-Cliq Component Read Parameter Value; Read DQ Value; DRIVE-Cliq Component Versions; DQ Comp Version; Firmware Update Automatic; FW Update Auto

Siemens SINAMICS DCM
1204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS DCM
296 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the parameter index to access a parameter of a DRIVE-CLiQ component.
Dependency: Refer to: p7820, p7821, r7823
Description: Displays the parameter value read from the DRIVE-CLiQ component.
Dependency: Refer to: p7820, p7821, p7822
Description: Displays the firmware and EEPROM versions of the DRIVE-CLiQ component selected using p7828[1].
Index: [0] = Reference firmware version
[1] = Actual firmware version
[2] = EEPROM0 version
[3] = EEPROM1 version
[4] = EEPROM2 version
[5] = EEPROM3 version
[6] = EEPROM4 version
Dependency: Refer to: p7828
Note: Re index 0:
Firmware version on the memory card/device memory.
Re index 1:
Actual firmware version of the DRIVE-CLiQ component.
Re index 2 ... 6:
Actual EEPROM version of the DRIVE-CLiQ component.
Description: Sets the behavior for the automatic firmware update of the DRIVE-CLiQ components.
p7822 DRIVE-CLiQ component parameter index / DQ para_index
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
r7823 DRIVE-CLiQ component read parameter value / Read DQ value
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r7825[0...6] DRIVE-CLiQ component versions / DQ comp version
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p7826 Firmware update automatic / FW update auto
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1

Table of Contents

Other manuals for Siemens SINAMICS DCM