EasyManua.ls Logo

Siemens SINAMICS DCM - CO;BO: Armature Auto-Reversing Stage State; Arm Stage State; CO;BO: RFG State; RFG State

Siemens SINAMICS DCM
1204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
639
2 Parameters
2.2 List of parameters
Description: Displays the state of the ramp-function generator.
Description: Displays the state of the auto-reversing stage.
Bit field: Bit Signal name 1 signal 0 signal FP
04 Direction of rotation enable No enable Enable 3135
08 Jog ON command ON OFF 3125
09 Creep ON command ON OFF 3130
10 Fixed setpoint bypass ramp-function
generator
ON OFF 3115
11 Jog setpoint bypass ramp-function
generator
ON OFF 3125
12 Creep setpoint bypass ramp-function
generator
ON OFF 3130
13 Fixed setpoint input active Yes No 3115
14 Setpoint from AOP/PC active Yes No 3113
15 Jog setpoint is zero Yes No 3125
r53171.0...5 CO/BO: RFG state / RFG state
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 3150, 3151,
3152, 3155
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Limiting active after ramp-function generator Yes No 3155
01 RFG output equals zero Yes No 3152
02 RFG ramping up Yes No 3150,
3152
03 RFG ramping down Yes No 3150,
3152
04 RFG setpoint enable present Yes No 3151
05 RFG active Yes No 3150
r53190.0...12 CO/BO: Armature auto-reversing stage state / Arm stage state
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 6815, 6855,
6860, 6862, 8046
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Torque direction enabled M0 or MI M0 or MII -
01 Torque direction I active Yes No -
02 Torque direction II active Yes No -
03 Torque direction 0 requested Yes No -
04 Torque direction I requested Yes No -
05 Torque direction II requested Yes No -
06 Torque direction change in progress Yes No -
07 Alpha G limit reached Yes No -
08 Alpha W limit reached Yes No -
09 Alpha G limit or Alpha W limit reached Yes No -
10 Positive limit of n, M, I, Alpha reached Yes No -
11 Negative limit of n, M, I, Alpha reached Yes No -
12 Alpha W shift active Yes No -

Table of Contents

Other manuals for Siemens SINAMICS DCM

Related product manuals