SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
191
2 Parameters
2.2 List of parameters
Description: Sets the operating mode for the energy-saving mode function.
Value: 0: Energy-saving mode inhibited
1: Energy-saving mode activated
Dependency: Refer to: p2200
Caution: When this function is active, the motor can start again automatically.
Note: When the energy-saving mode function (p2398 = 1) is activated, its behavior is defined as to whether the technology
controller is additionally switched in (closed-loop) or switched out (open-loop).
The technology controller is enabled via binector input p2200 and its mode is set in p2251.
p2200 = 0, p2251 = 0, 1:
Energy-saving mode operates without technology controller (open-loop)
p2200 = 1, p2251 = 0:
Energy-saving mode operates with technology controller (closed-loop)
p2200 = 1, p2251 = 1:
Energy-saving mode operates without technology controller (open-loop) as its output is only used as supplementary
setpoint and not as main setpoint.
Description: Sets the motor revolutions for the gearbox factor between the motor shaft and load shaft.
Gearbox factor = motor revolutions (p2504) / load revolutions (p2505)
Dependency: Refer to: p0432, p0433, p2505
Note: The gearbox factor between the encoder shaft and the motor shaft is set using p0432 and p0433.
Description: Sets the load revolutions for the gearbox factor between the motor shaft and load shaft.
Gearbox factor = motor revolutions (p2504) / load revolutions (p2505)
Dependency: Refer to: p0432, p0433, p2504
Note: The gearbox factor between the encoder shaft and the motor shaft is set using p0432 and p0433.
10 Technology controller output at the
minimum
Yes No -
11 Technology controller output at the
maximum
Yes No -
p2398 Energy-saving mode / En_save mode
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p2504[0...n] LR motor/load motor revolutions / Mot/load motor rev
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: C2(4) Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: DDS, p0180 Func. diagram: 4704, 4711
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 1048576 1
p2505[0...n] LR motor/load load revolutions / Mot/load load rev
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: C2(4) Calculated: - Access level: 1
Data type: Integer32 Dyn. index: DDS, p0180 Func. diagram: 4704, 4711
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-1048576 1048576 1