4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCM
1160 List Manual (LH8), 02/2015, 6RX1800-0ED76
F60063 (N, A) Incorrect calibration values for analog inputs/outputs
Message value: %1
Message class: General drive fault (19)
Drive object: DC_CTRL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: The factory-set calibration values on the electronics module for the analog inputs/outputs are implausible.
Fault value (r0949, interpret decimal):
1: Analog input 0 (X177.25/26), voltage input, offset incorrect value
2: Analog input 0 (X177.25/26), voltage input, +10 V incorrect value
3: Analog input 0 (X177.25/26), voltage input, -10 V incorrect value
4: Analog input 0 (X177.25/26), voltage input, reference value incorrect
5: Analog input 0 (X177.25/26), current input, offset incorrect value
6: Analog input 0 (X177.25/26), current input, +20 mA incorrect value
7: Analog input 0 (X177.25/26), current input, -20 mA incorrect value
8: Analog input 0 (X177.25/26), current input, reference value incorrect
9: Analog input 1 (X177.27/28), voltage input, offset incorrect value
10: Analog input 1 (X177.27/28), voltage input, +10 V incorrect value
11: Analog input 1 (X177.27/28), voltage input, -10 V incorrect value
12: Analog input 1 (X177.27/28), voltage input, reference value incorrect
13: Analog input 1 (X177.27/28), current input, offset incorrect value
14: Analog input 1 (X177.27/28), current input, +20 mA incorrect value
15: Analog input 1 (X177.27/28), current input, -20 mA incorrect value
16: Analog input 1 (X177.27/28), current input, reference value incorrect
17: Analog input 2 (X177.29/30), voltage input, offset incorrect value
18: Analog input 2 (X177.29/30), voltage input, +10 V incorrect value
19: Analog input 2 (X177.29/30), voltage input, -10 V incorrect value
20: Analog input 2 (X177.29/30), voltage input, reference value incorrect
21: Analog input 3 (X177.1/2), voltage input, offset incorrect value
22: Analog input 3 (X177.1/2), voltage input, +10 V incorrect value
23: Analog input 3 (X177.1/2), voltage input, -10 V incorrect value
24: Analog input 3 (X177.1/2), voltage input, reference value incorrect
25: Analog input 4 (X177.3/4), voltage input, offset incorrect value
26: Analog input 4 (X177.3/4), voltage input, +10 V incorrect value
27: Analog input 4 (X177.3/4), voltage input, -10 V incorrect value
28: Analog input 4 (X177.3/4), voltage input, reference value incorrect
29: Analog input 5 (X177.5/6), voltage input, offset incorrect value
30: Analog input 5 (X177.5/6), voltage input, +10 V incorrect value
31: Analog input 5 (X177.5/6), voltage input, -10 V incorrect value
32: Analog input 5 (X177.5/6), voltage input, reference value incorrect
33: Analog input 6 (X177.7/8), voltage input, offset incorrect value
34: Analog input 6 (X177.7/8), voltage input, +10 V incorrect value
35: Analog input 6 (X177.7/8), voltage input, -10 V incorrect value
36: Analog input 6 (X177.7/8), voltage input, reference value incorrect
37: Analog input XT1.103/104, voltage input, offset incorrect value
38: Analog input XT1.103/104, voltage input, +25 V incorrect value
39: Analog input XT1.103/104, voltage input, -25 V incorrect value
40: Analog input XT1.103/104, voltage input, reference value incorrect
41: Analog input XT1.103/104, voltage input, offset incorrect value
42: Analog input XT1.103/104, voltage input, +80 V incorrect value
43: Analog input XT1.103/104, voltage input, -80 V incorrect value
44: Analog input XT1.103/104, voltage input, reference value incorrect
45: Analog input XT1.103/104, voltage input, offset incorrect value
46: Analog input XT1.103/104, voltage input, +270 V incorrect value

Table of Contents