2 Parameters
2.2 List of parameters
SINAMICS DCM
416 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the signal source for changeover between closed-loop current control and closed-loop torque control.
p50170 = 0 and p50173 = 0 signal:
The controller is current-controlled.
p50170 = 1 or p50173 = 1 signal:
The controller is torque-controlled; in other words, the torque setpoint is converted into a current setpoint (current
setpoint = torque setpoint/motor flux).
Dependency: If p50169 or p50170 is set to a value of 1, there must be a valid field characteristic (p50117 = 1); otherwise fault
F60055 will be output on power-up. If this setting is selected, the optimization run for field weakening must be
performed in advance (p50051 = 27).
Parameter p50263 defines the input variable for determining the motor flux.
Refer to: p50170
Note: The following parameters are used to change over between current control and torque control:
- Signal source via connector input p50173
or
- Fixed set value in p50170
Description: Value = 0 --> torque limiting is not bypassed for OFF1 & OFF3
Value = 1 --> torque limiting bypass active for OFF1 & OFF3
Factory setting = 1 (for compatibility reasons)
Value: 0: Torque limiting for OFF1 & OFF3 active
1: Torque limiting for OFF1 & OFF3 not active
Dependency: Refer to: r52133, r52147
Description: Sets the signal source for variable control of the armature current controller's P gain.
Dependency: Refer to: p50155
Note: The P gain (Kp) for the armature current controller is calculated as follows:
Kp = p50155 x |p50175|
p50173[0...n] BI: Signal source for closed-loop current/torque control ctr type / Ctr I/tq ctr sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 6835
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p50174 Torque limiting for OFF1 & OFF3 / T_lim OFF1 & OFF3
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 6840
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 1
p50175[0...n] CI: Signal source for closed-loop armature current control P gain / Ia ctr Kp sig s
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 6855
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 1

Table of Contents

Other manuals for Siemens SINAMICS DCM