2 Parameters
2.2 List of parameters
SINAMICS DCM
532 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Displays the I2t value for the voltage limiting chopper 1 for Converter Commutation Protector (CCP).
Description: Displays the I2t value for the voltage limiting chopper 2 for Converter Commutation Protector (CCP).
Description: Sets the upper response threshold of the voltage limiter implemented in the CCP.
During the turn-off operation of the CCP when reducing the armature current, this limits the counter voltage that is
created - and which is also necessary - to a non-hazardous value for the basic device and for the associated CCP.
Note: CCP: Converter Commutation Protector
The parameter is set automatically during the "optimization run for CCP" (p50051 = 30).
The correct setting of this parameter can be taken from the following reference:
SIMOREG CCP Operating Instructions
Description: Sets the minimum charging voltage required for the turn-off capacitors used in the CCP to successfully turn off the
thyristors.
This value is used as setpoint for the two-level controller, which precharges the turn-off capacitors from the line
supply.
The maximum pre-charging voltage that can be reached is limited by the average rectified value of the line voltage
that is actually connected.
Note: CCP: Converter Commutation Protector
The parameter is set automatically during the "optimization run for CCP" (p50051 = 30).
The correct setting of this parameter can be taken from the following reference:
SIMOREG CCP Operating Instructions
r51575 CO: CCP I2t value voltage limiting chopper 1 / CCP I2t chopper 1
DC_CTRL Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6970
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r51576 CO: CCP I2t value voltage limiting chopper 2 / CCP I2t chopper 2
DC_CTRL Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6970
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p51577 CCP chopper voltage setpoint response threshold upper / CCP V_set thr up
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6970
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
850 [V] 2900 [V] 1600 [V]
p51578 CCP turn-off capacitors pre-charging voltage setpoint / C pre-ch V_set
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6970
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
145 [V] 830 [V] 145 [V]